Shipping included*
Exclusions
Additional shipping fees may apply in rare circumstances for deliveries outside standard service areas. In most cases, this only potentially affects shipments to the Northwest Territories and Yukon, as well as certain heavy or oversized items.
Minuteman ED8KRT-5KTF Endeavor 8000VA Rack/Tower UPS - 5U Double Conversion Online - 6. 98 kW - 120/230V AC Input
Business volume discounts
Technical guidance
Preparation & staging
QC · ON · AB · BC
Product Features
Technical Overview
This double conversion online UPS continuously converts incoming AC power to DC and back to AC, providing complete isolation from utility power anomalies. The output delivers a stable true sine wave at voltages including 208 V AC, 220 V AC, 230 V AC, 240 V AC, 120 V AC, 110 V AC, and 115 V AC, with frequency synchronization at 50 Hz or 60 Hz.
The unit accepts a wide input voltage range from 0 V AC to 300 V AC, with an operational window of 180 V AC to 280 V AC, accommodating unstable grid conditions. It incorporates a 3140 J surge energy rating and a built-in circuit breaker for overload protection.
This section brings together practical product details such as Plug/Connector Type, Phase, Efficiency Detail, Load Capacity (VA), so buyers can judge configuration, deployment fit, and day-to-day suitability with less guesswork.
Key Product Advantages
The Endeavor ED8KRT-5KTF combines high power density with flexible deployment options and robust management features for critical infrastructure protection.
High Power Density in 5U Form Factor
Delivers 8 kVA and 6.98 kW of protected power within a compact 5U rack space, maximizing power per rack unit for data center and server room efficiency.
- 5U rack height
- Rack/tower convertible design
- 292.03 lb weight
Hot-Swappable Battery System
Allows battery replacement without shutting down connected equipment, ensuring uninterrupted power protection during maintenance and extending system uptime.
- User-replaceable batteries
- No downtime for battery swaps
- Supports continuous operation
Comprehensive Management Interfaces
Includes RS-232 for network management, USB for local monitoring, and an EPO (Emergency Power Off) port for safety integration, providing full control and visibility.
- RS-232 serial port
- USB connectivity
- EPO safety port
Deployment / Use Cases
This UPS is designed for environments where power quality and availability directly impact operational continuity and data integrity. Its double conversion topology and high capacity make it suitable for protecting sensitive electronic equipment from all common power disturbances.
Typical deployments include server racks in data centers and enterprise server rooms, network operation centers supporting telecommunications and VoIP systems, industrial control panels in manufacturing facilities, and security infrastructure requiring 24/7 availability. The hardwired connection and rack/tower flexibility support both dedicated rack installations and standalone tower configurations in equipment rooms.
Data Center Server Protection
Provides clean power to blade servers, storage arrays, and networking gear, with runtime to support graceful shutdowns or transfer to backup generators during extended outages.
Industrial & Infrastructure Applications
Protects PLCs, SCADA systems, and telecommunications equipment in environments with unstable power, with wide input voltage ranges and robust environmental tolerances.
Physical Profile
The UPS measures 11.95" in height, 17.24" in width, and 28.74" in depth, occupying 5U of rack space. Its rack/tower convertible design includes integrated mounting hardware for standard 19-inch racks, while the tower configuration offers stability for standalone use. The unit weighs 292.03 lb, requiring proper handling equipment for installation. It operates in temperatures from 32°F to 104°F with 0% to 95% humidity tolerance, and can be installed at elevations up to 15,000 feet.
- Width
- 17.24" (437.90 mm)
- Height
- 11.95" (303.53 mm)
- Weight
- 292.03 lb (132462.58 g)
- Length
- 28.74" (730 mm)
What's in the Box
The package includes the Endeavor ED8KRT-5KTF 8000VA Rack/Tower UPS unit and necessary communication cables for management interface connectivity.
Package contents include Endeavor ED8KRT-5KTF 8000VA Rack/Tower UPS Comm. Cables, Endeavor ED8KRT-5KTF 8000VA Rack/Tower UPS. These included items support setup, installation, and immediate deployment without needing to source the core bundled accessories separately.
Highlights
- 8 kVA / 6.98 kW double conversion online UPS for critical IT and industrial loads
- True sine wave output ensures compatibility with sensitive servers and network equipment
- 3-minute runtime at full load, 11 minutes at half load for graceful shutdowns
- Hot-swappable, user-replaceable batteries support maintenance without downtime
- 5U rack/tower convertible design maximizes power density in server racks
- Wide input voltage range (0-300 V AC) accommodates unstable utility power
- RS-232, USB, and EPO ports provide comprehensive management and safety integration
- 93% efficiency in AC mode reduces operational power costs
- ENERGY STAR 2.0 certified for energy efficiency compliance
- 3-year warranty covering electronics and batteries
Specifications
| Specifications | |
|---|---|
| Manufacturer | Para Systems, Inc |
| Manufacturer Part Number | ED8KRT-5KTF |
| Brand Name | Minuteman |
| Product Line | Endeavor |
| Product Model | ED8KRT-5KTF |
| Product Name | Endeavor ED8KRT-5KTF 8000VA Rack/Tower UPS |
| Product Type | Double Conversion Online UPS |
| Technical Information | |
| Plug/Connector Type | Hardwired |
| Phase | Single Phase |
| Efficiency Detail | 93% (AC Mode) |
| Application/Usage | IT,Telecommunication,Security,Business,Infrastructure,Server,Network,Industrial,Enterprise Installation,Corporate,VoIP |
| Surge Suppression | Yes |
| Features | Cold Start Function |
| Power Description | |
| Load Capacity (VA) | 8 kVA |
| Load Capacity (Watt) | 6.98 kW |
| Input Voltage | 120 V AC,230 V AC |
| Input Voltage Range | 0 V AC - 300 V AC,180 V AC - 280 V AC |
| Input Current | 51 A |
| Output Voltage | 208 V AC,220 V AC,230 V AC,240 V AC,120 V AC,110 V AC,115 V AC |
| Input Frequency | 40 Hz,70 Hz |
| Output Frequency | 50 Hz,60 Hz |
| Waveform Type | True Sine Wave |
| Surge Energy Rating | 3140 J |
| Circuit Breaker | Yes |
| Display & Graphics | |
| Display | LCD |
| Management | |
| Network Management | RS-232 |
| Interfaces/Ports | |
| Serial Port | Yes |
| USB | Yes |
| EPO Port | Yes |
| Battery Information | |
| Backup/Run Time (Full Load) | 3 Minute |
| Backup/Run Time (Half Load) | 11 Minute |
| Hot Swappable | Yes |
| Replaceable Battery | Yes |
| Environmental Conditions | |
| Maximum Operating Elevation | 15000 ft (4572000 mm) |
| Maximum Storage Elevation | 50000 ft (15240000 mm) |
| Storage Temperature | 5°F (-15°C) - 131°F (55°C) |
| Operating Humidity | 0% - 95% |
| Storage Relative Humidity | 0% - 95% |
| Minimum Operating Temperature | 32°F (0°C) |
| Maximum Operating Temperature | 104°F (40°C) |
| Physical Characteristics | |
| Height | 11.95" (303.53 mm) |
| Width | 17.24" (437.90 mm) |
| Length | 28.74" (730 mm) |
| Rack Height | 5U |
| Form Factor | Rack/Tower |
| Weight (Approximate) | 292.03 lb (132462.58 g) |
| Miscellaneous | |
| Package Contents | Endeavor ED8KRT-5KTF 8000VA Rack/Tower UPS Comm. Cables |
| Energy Star | Yes |
| Energy Efficiency Certification | ENERGY STAR 2.0 |
| Environmental Compliance | Restriction of Hazardous Substances (RoHS) 2 |
| Warranty | |
| Limited Warranty | 3 Year |
| Additional Warranty Information | 3 Years (Electronics and Batteries) |
User Manual
FAQ
What is the power capacity of this Minuteman UPS?
The Minuteman Endeavor ED8KRT-5KTF provides 8 kVA (8000 VA) and 6.98 kW of power capacity. This double conversion online UPS can support substantial IT loads including servers, network switches, storage systems, and telecommunications equipment, delivering clean, regulated power during utility outages or disturbances.
How long will this UPS run on battery power?
At full load (6.98 kW), the UPS provides approximately 3 minutes of runtime. At half load (3.49 kW), runtime extends to about 11 minutes. These runtimes allow sufficient time for connected equipment to perform graceful shutdowns or for backup generators to start and stabilize during extended power interruptions.
Can this UPS be installed in a server rack?
Yes, the Endeavor ED8KRT-5KTF is designed for both rack and tower deployment. It occupies 5U of rack space in a standard 19-inch rack, with dimensions of 11.95" height, 17.24" width, and 28.74" depth. The unit includes integrated mounting hardware and can also be used as a standalone tower for flexibility in equipment rooms.
What input voltages does this UPS accept?
The UPS accepts input voltages of 120 V AC and 230 V AC, with a wide operational range from 180 V AC to 280 V AC. It can tolerate input voltages from 0 V AC to 300 V AC, making it suitable for environments with unstable utility power or voltage fluctuations.
What management interfaces are available?
Management interfaces include RS-232 for network management connectivity, USB for local monitoring and configuration, and an EPO (Emergency Power Off) port for safety system integration. These interfaces provide comprehensive control, monitoring, and shutdown capabilities for the UPS and connected equipment.
Are the batteries user-replaceable?
Yes, the batteries are hot-swappable and user-replaceable. This design allows battery replacement without shutting down the UPS or connected equipment, ensuring continuous power protection during maintenance. The 3-year warranty covers both electronics and batteries for comprehensive protection.
What power capacity is listed for this UPS?
The listed power specification is 8 kVA, which helps position the unit for the right load level and installation role.
What voltage details are listed?
The listed power specification is 120 V AC,230 V AC, which helps position the unit for the right load level and installation role.